Product Description



Product Specification
Model |
|
GT-SKR020KBDC-S32 |
GT-SKR030KBDC-S32 |
GT-SKR040KBDC-S32 |
GT-SKR050KBDC-S32 |
Heating at A7/W35 |
|
|
|
|
|
Heating capacity (min-max) |
KW |
6.80 (3.36-7.93) |
9.00 (4.50-10.66) |
12.80 (6.05-14.30) |
17.00 (8.60-20.30) |
Power input (min-max) |
KW |
1.62 (0.82-1.91) |
2.05 (1.07-2.50) |
2.97 (1.51-3.52) |
3.86 (1.91-4.45) |
COP |
W/W |
4.20 (3.30-5.40) |
4.40 (3.30-5.30) |
4.30 (3.20-5.20) |
4.40 (3.30-5.50) |
Heating at A2/W35 |
|
|
|
|
|
Heating capacity (min-max) |
KW |
6.25 (2.92-7.42) |
8.32 (3.74-9.52) |
11.80 (5.30-13.30) |
15.70 (7.37-18.80) |
Power input (min-max) |
KW |
1.60 (0.82-1.96) |
2.03 (1.02-2.45) |
2.95 (1.45-3.50) |
3.84 (1.89-4.56) |
COP |
W/W |
3.90 (2.30-4.60) |
4.10 (2.40-4.60) |
4.00 (2.20-4.40) |
4.10 (2.40-4.80) |
Cooling at A35/W7 |
|
|
|
|
|
Cooling capacity (min-max) |
KW |
5.00 (2.75-6.50) |
6.50 (3.58-8.45) |
10.20 (5.61-13.26) |
12.90 (7.10-18.70) |
Power input (min-max) |
KW |
1.78 (1.07-2.58) |
2.28 (1.37-3.31) |
3.64 (2.18-5.28) |
4.45 (2.67-6.45) |
EER |
W/W |
2.80 (2.40-3.15) |
2.85 (2.45-3.15) |
2.80 (2.40-3.10) |
2.90 (2.45-3.20) |
SCOP |
|
|
|
|
|
SCOP (TWW for 35ºC) |
N/A |
4.48 |
4.57 |
4.69 |
4.67 |
Energy label |
N/A |
A+++ |
A+++ |
A+++ |
A+++ |
|
|
|
|
|
|
Power supply |
V/Ph/Hz |
220-240/1/50 |
220-240/1/50 |
220-240/1/50 |
380-415/3/50 |
Compressor type |
N/A |
DC Inverter |
DC Inverter |
DC Inverter |
DC Inverter |
Fan type |
N/A |
DC |
DC |
DC |
DC |
Refrigerant |
N/A |
R32 (0.75kg) |
R32 (1.80kg) |
R32 (2.00kg) |
R32 (2.20kg) |
Refrigerant regulation |
N/A |
Electronic expansion valve |
Heat exchanger type |
N/A |
Brazed plate heat exchanger |
Water connection |
Inch |
1 |
1 |
1 |
1 |
Norminal water flow |
m3/h |
1.4 |
1.8 |
2.7 |
3.6 |
Operating outdoor temperature |
ºC |
-20~43 |
-20~43 |
-20~43 |
-20~43 |
Max heating temperature |
ºC |
60 |
60 |
60 |
60 |
Max DHW temperature |
ºC |
55 |
55 |
55 |
55 |
Min cooling water temperature |
ºC |
10 |
10 |
10 |
10 |
Sound level |
dB(A) |
52 |
54 |
56 |
56 |
Degree of protection |
N/A |
IPX4 |
IPX4 |
IPX4 |
IPX4 |
Net weight (outdoor unit) |
kg |
57 |
72 |
102 |
122 |
Net weight (indoor unit) |
kg |
21 |
22 |
22.5 |
23 |
Dimension (outdoor unit) |
mm |
945*410*600 |
1010*410*795 |
1115*470*1020 |
1165*470*1280 |
Dimension (indoor unit) |
mm |
460*230*635 |
460*230*635 |
460*230*635 |
460*230*635 |
Test condition:
1. A7/W35: outdoor air temperature 7ºC DB/6ºC WB, water inlet/outlet temperature 30ºC/35ºC
2. A2/W35: outdoor air temperature 2ºC DB/1ºC WB, water inlet/outlet temperature 30ºC/35ºC
3. A35/W7: outdoor air temperature 35ºC, water inlet/outlet temperature 12ºC/7ºC
Q1 |
How about your delivery time ? |
A1 |
Generally, it will take 35 to 40 days after receiving your advance payment. The specific delivery time depends on the items and the quantity of your order. |
Q2 |
What is your term of delivery ? |
A2 |
EXW, FOB, LC, etc |
Q3 |
What is your terms of packing? |
A3 |
Generally, we pack the heat pump in brown cartons or plywood. If you have legally registered patent, we can pack the heat pump in your branded boxes after getting your authorization letters. |
Q4 |
What is your sample policy? |
A4 |
We accept the sample order, but the customers have to pay the sample cost and the courier cost. |
Q5 |
Do you test all your goods before delivery? |
A5 |
Yes, we have 100% test before we pack the goods for delivery |
Q6 |
How long is the guarantee time? |
A6 |
3-year warranty on the whole unit. The spare parts must be non-humanly damaged, usually we give to customer 1.5% spare parts free of charge for maintenance according to order cost during the warranty period. |